Central loose tube, gel-free cable, RP-rodent protected, indoor-use, FRLSZH shea - eCatalog

eCatalog

Central loose tube, gel-free cable, RP-rodent protected, indoor-use, FRLSZH sheath - orange, B2ca, 01 x 08 fibers OM2

Article no.: R857770
EAN / GTIN: 7611821017868
Delivery Unit: 1
Unit of Measure: M

Rodent protected, non-metallic and dry central loose tube cable for up to a maximum of 24 fibers for indoor duct installation.

Technical Data
Cable family code IFEF FiRis
Cable type Central loose tube cable
Cable version Gel-free installation cable
Cable application indoor use
CPR classification B2ca-s1a,d0,a1
DoP number D9082
Fiber type OM2
Fiber count 8
Fiber color coding 1.-12.: red, green, blue, yellow, white, gray, brown, violet, turquoise, black, orange, pink13.-24.: red, green, blue, yellow, white, gray, brown, violet, turquoise, natural, orange, pink(ring-marked)
Fiber count per tube 24
Loose tube count 1
Loose tube diameter 2.4 mm
Armor Rodent protection
Outer sheath thickness 0.9 mm
Outer sheath material FRLSZH
Outer sheath color orange
Cable outer diameter 5.4 mm
Cable weight 32.0 kg/km / 21 lbs/1000ft
DIN / VDE 0888 code J-B(ZN)H
CPR test method EN 50575, EN 13501-6
Standard put-up length on drum 2100 m ± 5%
CPR classification B2ca
Mechanical Data
Installation tensile strength 1000 N (5 min.)
Installation tensile strength acceptance criteria Δα ≤ 0,05 dB after test
Installation tensile strength test method IEC 60794-1-21:E1A
Crush resistance long term 500 N/100mm (15min)
Long-term crush resistance acceptance criteria Δα ≤ 0,05 dB prior release, no damage
Long-term crush resistance test method IEC 60794-1-21:E3A
Short-term crush resistance 1000 N/100mm
Short-term crush resistance acceptance criteria Δα ≤ 0,05 dB after release, no damage
Short-term crush resistance test method IEC 60794-1-21:E3A
Impact resistance 5 Nm, 3 impacts, d=20 mm, R=12,5 mm
Impact resistance acceptance criteria no fiber breakage
Impact resistance test method IEC 60794-1-21:E4
Torsion L = 1 m, rotation angle ±180°, 10 cycles, F= 20N
Torsion acceptance criteria no fiber breakage
Torsion test method IEC 60794-1-21:E7
Kink d=20 x cable diameter
Kink acceptance criteria no kink
Repeated bending R=10 x cable diameter, 25 cycles, m = 4Kg
Repeated bending acceptance criteria no damage
Repeated bending test method IEC 60794-1-21:E6
Cable bend R=20 x cable diameter, 6 turns, 10 cycles
Cable bend acceptance criteria no fiber breakage
Cable bend test method IEC 60794-1-21:E11A
Minimum bend radius in service 85 mm
Minimum bend radius during installation 110 mm
Environmental Characteristics
Temperature cycling -20 °C +60 °C / -4 °F +140 °F
Temperature cycling acceptance criteria Δα ≤ 0,05 dB
Temperature cycling test method IEC 60794-1-22:F1
Reversible temperature cycling -25 °C +60 °C / -13 °F +140 °F
Reversible temperature cycling acceptance criteria Δα ≤ 0,15 dB, reversible
Reversible temperature cycling test method IEC 60794-1-22:F1
Operation temperature -20 °C to +60 °C / -4 °F to +140 °F
Storage / Transport temperature -25 °C to +60 °C / -13 °F to +140 °F
Thermal load 0.48 MJ/m