Central loose tube, single sheathed cable, RP-rodent protected, universal-use, UV.FRLSZH sheath - green, Dca, 01 x 06 fibers OM1

Article no.: R855524
EAN / GTIN: 7611821025160
Delivery Unit: 2.100
Unit of Measure: M

Rodent protected, non-metallic central loose tube cable for up to a maximum of12 fibers for indoor or outdoor duct installation.

Technical Data
Cable family code UT1EF
Cable type Central loose tube cable
Cable version n.a.
Cable application universal use
CPR classification Dca-s2,d1,a1
DoP number D9012
Fiber type OM1
Fiber count 6
Fiber color coding 1.-12.: red, green, blue, yellow, white, gray, brown, violet, turquoise, black, orange, pink
Fiber count per tube 12
Loose tube count 1
Loose tube diameter 2.3 mm
Armor Rodent protection
Outer sheath thickness 1 mm
Outer sheath material UV stable FRLSZH
Outer sheath color green
Sheath marking Ink-Jet, black
Cable outer diameter 5.2 mm
Cable weight 33.0 kg/km / 22 lbs/1000ft
DIN / VDE 0888 code U-DQ(ZN)H
CPR test method EN 50575, EN 13501-6
Standard put-up length on drum 2100/m ± 5%
CPR classification Dca
Mechanical Data
In-service tensile strength 300 N
In-service tensile strength acceptance criteria Δα ≤ 0,05 dB
In-service tensile strength test method IEC 60794-1-21:E1
Installation tensile strength 1000 N
Installation tensile strength acceptance criteria Δα ≤ 0,05 dB after test
Installation tensile strength test method IEC 60794-1-21:E1
Crush resistance long term 1000 N/100mm
Long-term crush resistance acceptance criteria Δα ≤ 0,05 dB prior release, no damage
Long-term crush resistance test method IEC 60794-1-21:E3A
Short-term crush resistance 2000 N/100mm
Short-term crush resistance acceptance criteria Δα ≤ 0,05 dB after release, no damage
Short-term crush resistance test method IEC 60794-1-21:E3A
Impact resistance 10 Nm, 3 impacts, d=20 mm, R=300 mm
Impact resistance acceptance criteria Δα ≤ 0,05 dB after test, no damage
Impact resistance test method IEC 60794-1-21:E4
Torsion L = 1 m, rotation angle ±180°, 10 cycles
Torsion acceptance criteria no damage
Torsion test method IEC 60794-1-21:E7
Repeated bending R=20 x cable diameter, 25 cycles
Repeated bending acceptance criteria no damage
Repeated bending test method IEC 60794-1-21:E6
Cable bend d=20 x cable diameter, 4 turns, 3 cycles
Cable bend acceptance criteria Δα ≤ 0,05 dB after test, no damage
Cable bend test method IEC 60794-1-21:E11A
Minimum bend radius in service 80 mm
Minimum bend radius during installation 120 mm
Environmental Characteristics
Temperature cycling -40 °C +70 °C / -40 °F +158 °F
Temperature cycling acceptance criteria Δα ≤ 0,05 dB
Temperature cycling test method EN 60794-1-22:F1
Operation temperature -40 °C to +70 °C / -40 °F to +158 °F
Storage / Transport temperature -40 °C to +70 °C / -40 °F to +158 °F
Water penetration L = 3 m, h = 1 m, 24 h
Water penetration acceptance criteria no water leakage
Water penetration test method IEC 60794-1-22 F5B
Thermal load 0.48 MJ/m
Flammability vertical single cable Pass
Flammability vertical single cable test method IEC 61034-2
Flammability vertical cable bundle Pass
Flammability vertical cable bundle test method IEC 60332-3-22
Smoke density Pass
Smoke density test method IEC 61034-1, IEC 61034-2
Halogen free, acid gases Pass
Halogen free, acid gases test method IEC 60754-2
2015 / 863 / EU - RoHS 3 Pass